Description
The Cooper Power Systems Current Sensing Bay-O-Net fuse link is used in Cooper Power Systems Bay-O-Net fuse assemblies to protect distribution apparatus from damaging currents and to protect distribution systems from failed apparatus. They are used on single-phase conventional and self-protected distribution transformers and other apparatus rated through 500 kVA, and on three-phase equipment through 1500 kVA.
A Bay-O-Net fuse is ideal for use in a two-fuse protection scheme with a current-limiting backup fuse. In this arrangement, secondary faults and overload currents are cleared by the Bay-O-Net fuse, and high level faults are cleared by the current-limiting fuse. The two fuses are connected in series, and are coordinated so that the current-limiting fuse operates only upon internal equipment failure. (See Section 240-50 to order an ELSP current-limiting backup fuse.) If the Bay-O-Net fuse will not be used in series with a current-limiting fuse, an isolation link is required.