S.T.A.R. Faulted Circuit Indicator (Electrostatic Reset Type) from Cooper Power Systems

General Product Information
ItemS.T.A.R. Faulted Circuit Indicator (Electrostatic Reset Type)
CompanyCooper Power Systems
Catalog Number
PriceRequest Quote
Quantity0
Manufacturer's CommentCooper Power Systems S.T.A.R. Electrostatic Reset (ER) faulted circuit indicators are designed to quickly and easily locate faulted sections of overhead distribution systems. These faulted circuit indicators (FCIs) can be installed on overhead distribution lines and derive their power from the voltage gradient between the line and the ground plane. This voltage gradient provides a reliable source for operating and resetting the fault indicator when compared to current reset devices which are subject to system loading variations. Electrostatic Reset FCIs provide a reliable means of fault location and isolation. In addition, they eliminate fault chasing methods which are costly and time consuming, and very stressful on system components exposed to the fault currents. Electrostatic Reset fault indicators have been designed to operate primarily on uninsulated, unshielded cable but may also be used on an unshielded insulated cable such as tree wire.
Operating Temperature -40°C to +85°C
Trip Current LevelFactory Preset (High and Low)
Trip Accuracy±10%
Fault Withstand25 kA for 10 cycles per IEEE 495™ Std -1986 standard
Battery1000 hours continuous 2.4 Ah Lithium Ion Battery (Internal, non-replaceable).
OptionsCan be equipped with an LED in addition to the Fis heye display.
More InformationCompany Product Page
Description
S.T.A.R. Electrostatic Reset fault indicators consist of a sensor unit with an integral Fis heye target display. The Fis heye display provides 180° visual indication. This unique orange reflective target designates a faulted condition and a black target designates a normal condition. The Fis heye display also features a Lexan® cover that provides superior scratch protection for the target window. The sensor unit itself features a clamping mechanism design that allows easy snap-on connection to the live conductor with the use of a single shotgun stick.

An inrush restraint feature eliminates false tripping and is standard on all units. The S.T.A.R. faulted circuit indicator will ignore inrush currents caused by reclosing operations of protective devices on the system. A dead time of 200 ms will activate the inrush restraint feature.

A low pass filter, also a standard feature, will prevent the S.T.A.R. faulted circuit indicator from tripping on high frequency transients like those caused by capacitive discharges.

In addition, the S.T.A.R. faulted circuit indicator is equipped with temperature compensation circuitry to assure the accurate and reliable performance over the entire specified temperature range.

The quick response time of the S.T.A.R. electrostatic reset faulted circuit indicator provides easy coordination with current-limiting fuses and other protective devices.This unique combination of standard features makes the S.T.A.R. faulted circuit indicator extremely reliable.