S.T.A.R.™ Faulted Circuit Indicators PATHFINDER™ (Variable Trip Test Point Type) from Cooper Power Systems

Inquire

from
Cooper Power Systems for
S.T.A.R.™ Faulted Circuit Indicators PATHFINDER™ (Variable Trip Test Point Type)

Description

The Variable Trip FCI is a one-piece housing that can be easily installed with a single shotgun stick using the pulling eye on the FCI. The sensor is designed to minimize proximity effect described as the sensitivity of FCIs to fault currents on other phases of a three-phase installation. The Variable Trip FCI indicates the passage of fault current by an integral high intensity LED display powered by a Lithium Ion battery. The sensor housing is made of durable, corrosion resistant materials. The electronic components are completely encapsulated to prevent environmental damage.

The Variable Trip design eliminates the need to specify a trip rating for the FCI. The load sensing feature adjusts the FCI to normal load conditions. When a fault occurs, the unit senses the rise in system current caused by the fault, followed by the loss of system voltage due to operation of the protective device. Thus, the Variable Trip FCI provides a “one size fits all”FCI for voltage test points, reducing inventory and eliminating problems caused by misapplication of FCIs.

  • Detailed Specifications
  • ItemS.T.A.R.™ Faulted Circuit Indicators PATHFINDER™ (Variable Trip Test Point Type)
  • CompanyCooper Power Systems
  • PriceInquire
  • Quantity0
  • manufacturer's comment

    Cooper Power Systems S.T.A.R.™PATHFINDER™ Variable Trip Test Point faulted circuit indicators (FCI) are designed to quickly and easily locate faulted sections of underground cable systems. These FCIs can be used on both 200 A separable connectors and 600 A terminators with a voltage test point. The removable sleeve allows for use on major manufacturers’ loadbreak elbows.

    The PATHFINDER Variable Trip Test Point FCI features a trip design that senses normal load current and indicates a fault when a significant rise in current, followed by a loss of voltage,is detected. Hence, there is no need to specify a particular trip rating when ordering the Variable Trip Test Point FCI. This design ensures fast, reliable and accurate operation.

    A long-life Lithium Ion battery provides power to indicate the faulted conditions using a high intensity light-emitting diode (LED) display. The unit will flash for a period of four hours after a fault has occurred. After the four hour period, the LED will stop flashing to conserve battery power; however, the unit retains a record of the fault event,and can be interrogated after the four hour period, using the manual testing/reset tool. The unit retains the memory of the fault event until reset manually,or until normal system power is restored.

    Variable Trip FCIs provide a reliable means of fault location and isolation.They also eliminate fault chasing methods that are costly and time consuming, and stressful on systemcomponents exposed to fault currents.

  • Operating Temperature -40°C to +85°C
  • Trip Current LevelVariable; 100 A rise from load current
  • Fault Withstand25 kA for 10 cycles per ANSI/IEEE 495-1986
  • Battery1.2 AH Lithium Ion Battery (non-replaceable)
  • optionsRemote Fiber Optic Display

    The Cooper Power Systems remote fiber optic display provides remote visual indication of the FCI operation. This display can be mounted in transformer and sector cabinets with a single hole installation. The remote fiber optic cable can be ordered using catalog number SFOC.

    Auxiliary Contacts

    Auxiliary Contacts can be added to the standard unit and provide an additional data collection point when used on circuits connected to a SCADA system. The magnetic latching circuit that operates the auxiliary contact ensures a reliable indication.