Padmount Faulted Circuit Indicators

Compare and Learn about Padmount Faulted Circuit Indicators

Select up to 5 products from below to compare or request more information.
  • Continuous Withstand Load:
  • Operating Temperature: -40°C to +85°C
  • Reset Time Accuracy:
  • Current Reset:
  • Trip Current Level: Factory Preset (High or Low)
  • Trip Accuracy: ±10%
  • Fault Withstand: 25 kA for 10 Cycles per ANSI/IEEE 495-1986
  • Battery:
  • Flag/LED Operating Life @ 23°C:
  • Strobe Operating Life @ 23°C:
  • Radio Operating Life @ 23°C:
  • Conductor Diameter Range: 0.25 inches (6.4 mm) to 1.0 inches (25 mm)
  • options: Remote FISHEYE™ Display

    The Cooper Power Systems Remote FISHEYE Display provides 180°visual indication of FCI operation. This unique orange reflective target fits a standard remote indicator window that exists in many pad-mounted transformer specifications.

    Small Remote Display

    The Current Reset Faulted Circuit Indicator is also available with a small remote display. The remote flip target display easily retrofits to pad-mounted cabinets with a single hole installation.

  • manufacturer's comment: Cooper Power Systems S.T.A.R.™ Current Reset (CR) Faulted Circuit Indicators are designed to quickly and easily locate faulted sections of cable systems. These faulted circuit indicators (FCIs) can be installed on pad-mounted distribution transformers, sector cabinets, switchgear and overhead bare conductors. The closed core current transformer (CT) senses the fault current and provides power to operate the FCI. The unit automatically resets back to the normal position when the continuous current exceeds the 2.4 A reset value. CR FCIs provide a reliable means of fault location and isolation. They also eliminate fault chasing methods that are costly and time consuming, and very stressful on system components exposed to fault currents. Installation can be achieved on a wide range of cable diameters with a single hotstick.
Read More
Inquire
Compare for selected.
  • Continuous Withstand Load:
  • Operating Temperature: -40°C to +85°C per ANSI/IEEE 495-1986
  • Reset Time Accuracy:
  • Current Reset:
  • Trip Current Level: Factory Preset (High or Low)
  • Trip Accuracy: ±10%
  • Fault Withstand: 10 kA for 10 Cycles per ANSI/IEEE 495-1986
  • Battery: 1.2 AH Lithium Ion Battery (non-replaceable)
  • Flag/LED Operating Life @ 23°C:
  • Strobe Operating Life @ 23°C:
  • Radio Operating Life @ 23°C:
  • Conductor Diameter Range:
  • options: Testing/Reset Tool

    The manual testing/reset tool can be ordered using catalog number SMRT.

  • manufacturer's comment:

    Cooper Power Systems S.T.A.R.™Delayed Reset (DR) faulted circuit indicators are designed to quickly and easily locate faulted sections of cable systems. These faulted circuit indicators (FCI) can be installed on padmounted distribution transformers,sector cabinets, switchgear and overhead bare conductors. A long-life Lithium Ion battery provides power to indicate the faulted conditions using a high intensity LED display. The unit automatically resets back to the normal position when reset time has expired. The unit can also be reset using the optional manual testing/reset tool. DR FCIs provide a reliable means of fault location and isolation. They also eliminate fault chasing methods that are costly and time consuming, and very stressful on system components exposed to fault currents. The DR FCI is ideally suited for temporary use as a testing tool. The delayed reset also allows the unit to be used to detect general fault location in applications where an intermittent fault causes recloser operation, but power is restored before the unit is interrogated.

Read More
Inquire
Compare for selected.
  • Continuous Withstand Load:
  • Operating Temperature: -40°C to +85°C
  • Reset Time Accuracy:
  • Current Reset:
  • Trip Current Level: Factory Preset (High and Low)
  • Trip Accuracy: ±10%
  • Fault Withstand: 25 kA for 10 cycles per ANSI/IEEE 495-1986
  • Battery: Two 1.2 AH Lithium Ion Batteries (20 Year Shelf Life)
  • Flag/LED Operating Life @ 23°C:
  • Strobe Operating Life @ 23°C:
  • Radio Operating Life @ 23°C:
  • Conductor Diameter Range:
  • options:
  • manufacturer's comment: Cooper Power Systems S.T.A.R.™Manual Reset (MR) faulted circuit indicators are designed to quickly and easily locate faulted sections of cable on distribution systems. These faulted circuit indicators (FCIs) can be installed on padmounted distribution transformers, sector cabinets,switchgear, and overhead distribution lines. Manual Reset FCIs provide a reliable means of fault location and isolation. In addition, they eliminate fault chasing methods which are costly and time consuming, and very stressful on system components exposed to the fault currents. Manual Reset faulted circuit indicators are designed to operate on overhead uninsulated,unshielded cable and unshielded insulated cable (such as tree wire), as well as concentric neutral and other cable, in underground, padmount and vault applications.
Read More
Inquire
Compare for selected.
  • Continuous Withstand Load:
  • Operating Temperature: -40°C to +85°C
  • Reset Time Accuracy:
  • Current Reset:
  • Trip Current Level: 100 A rise from load current
  • Trip Accuracy:
  • Fault Withstand: 25 kA for 10 Cycles per
  • Battery:
  • Flag/LED Operating Life @ 23°C:
  • Strobe Operating Life @ 23°C:
  • Radio Operating Life @ 23°C:
  • Conductor Diameter Range: 0.25 inches (6.4 mm) to 1.0 inches (25 mm)
  • options: Remote FISHEYE™ Display The Cooper Power Systems remote FISHEYE display provides 180°visual indication of FCI operation. This unique orange reflective target fits a standard remote indicator window that exists in many pad-mounted transformer specifications.Small Remote Display

    The Variable Trip Current Reset faulted circuit indicator is also available with a small remote display. The remote flip target display easily retrofits to pad-mounted cabinets with a single hole installation.Auxiliary Contacts

    Auxiliary Contacts can be added to the standard unit and provide an additional data collection point when used on circuits connected to a SCADA system. The magnetic latching circuit that operates the auxiliary contact ensures a reliable indication.

  • manufacturer's comment:

    PATHFINDER™ Variable Trip Current Reset (CR) faulted circuit indicators are designed to quickly and easily locate faulted sections of cable systems. These faulted circuit indicators (FCI)can be installed on pad-mounted distribution transformers, sector cabinets, switchgear and overhead bare conductors. The closed core current transformer (CT) senses the fault current and provides power to operate the FCI. The unit automatically resets back to the normal position when the continuous current exceeds the 2.0 A minimum reset value. CR FCIs provide a reliable means of fault location and isolation.

    The PATHFINDER Variable Trip Current Reset FCI features a trip design that senses normal load current and indicates a fault when a significant rise in current, followed by a loss of current,is detected. Hence, there is no need to specify a particular trip rating when ordering the Variable Trip Current Reset FCI. This design ensures fast,reliable and accurate operation. Variable Trip Current Reset FCIs provide a reliable means of fault location and isolation. They also eliminate fault chasing methods that are costly and time consuming, and stressful on system components exposed to faultcurrents.