3 Phase,Electro,Vacuum Intake 35kV

Compare and Learn about 3 Phase,Electro,Vacuum Intake 35kV

Select up to 5 products from below to compare or request more information.
  • nominal voltage: 34.5 kV
  • Maximum Continuous Current: 630/800/1200 A
  • Maximum Interrupting Current (symmetrical): 12500/16000 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Hydrophobic Cycloaliphatic Epoxy (HCEP)
  • Remote lockout indicator: Available
  • Standard bushing leakage distance to ground: 50.70 in. (1288 mm)
  • Alternative bushing leakage distance to ground: 14.40 in. (367 mm)
  • Available factory installed accessories: Supported communications technologies include: Wi-Fi, Cellular, Radio, Ethernet, SCADA, 900 MHz Spread and Spectrum
  • weight: 430 lbs. (195 kg)
  • Finish/color: Amber
  • manufacturer's comment: Benefits are:
    • Compact, lightweight design is easy to install, maneuver, and transport
    • Cast aluminum or 304 stainless steel protects high and low voltage cabinets from the elements
    • Variety of mounting frames offers maximum fl exibility
    • No electronics in high voltage cabinet protects controls from thermal overload
    • Simple-to-operate controller for easy logic based programming, training, and maintenance
    • Front panel of PCD allows direct access to system currents, recloser status, and settings
    • Voltage sensing saves space by eliminating bulky potential transformers Up to four individually programmable reclose cycles (up to fi ve shots to lockout)
    • Communications equipment fi ts right in control cabinet
    • 24 hour / 7 day dependable customer support.
    Stainless enclosure with no electronics in the high voltage compartment for easy maintenance. Pole or substation mounted. Incorporates integrated voltage and current sensors, and virtually maintenance free magnetic actuators. The PCD control offers advanced capabilities such as adaptive protection, control monitoring, power quality, communications, single phase tripping, and loop control.
Read More
Inquire
Compare for selected.
  • nominal voltage: 34.5 kV
  • Maximum Continuous Current: 630/800/1200 A
  • Maximum Interrupting Current (symmetrical): 12500/16000 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Hydrophobic Cycloaliphatic Epoxy (HCEP)
  • Remote lockout indicator: Available
  • Standard bushing leakage distance to ground: 50.70 in. (1288 mm)
  • Alternative bushing leakage distance to ground: 14.40 in. (367 mm)
  • Available factory installed accessories: Supported communications technologies include: Wi-Fi, Cellular, Radio, Ethernet, SCADA, 900 MHz Spread and Spectrum
  • weight: 430 lbs. (195 kg)
  • Finish/color: Amber
  • manufacturer's comment: Benefits are:
    • Compact, lightweight design is easy to install, maneuver, and transport
    • Cast aluminum or 304 stainless steel protects high and low voltage cabinets from the elements
    • Variety of mounting frames offers maximum fl exibility
    • No electronics in high voltage cabinet protects controls from thermal overload
    • Simple-to-operate controller for easy logic based programming, training, and maintenance
    • Front panel of PCD allows direct access to system currents, recloser status, and settings
    • Voltage sensing saves space by eliminating bulky potential transformers Up to four individually programmable reclose cycles (up to fi ve shots to lockout)
    • Communications equipment fi ts right in control cabinet
    • 24 hour / 7 day dependable customer support.
    Stainless enclosure with no electronics in the high voltage compartment for easy maintenance. Pole or substation mounted. Incorporates integrated voltage and current sensors, and virtually maintenance free magnetic actuators. The PCD control offers advanced capabilities such as adaptive protection, control monitoring, power quality, communications, single phase tripping, and loop control.
Read More
Inquire
Compare for selected.
  • nominal voltage: 34.5 kV
  • Maximum Continuous Current: 560 A
  • Maximum Interrupting Current (symmetrical): 12000 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Oil Insulated
  • Remote lockout indicator:
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories:
  • weight:
    • Weight without control : 1130 lbs.
    • Weight with pole-top frame : 1193 lbs.
    • Weight with substation frame : 1271 lbs.
  • Finish/color: The recloser head is an aluminum casting. The tank is fabricated of heavy-gauge steel and is finished with a corrosion-inhibiting-epoxy prime coat, followed by a finish coat of thermosetting acrylic paint. Finish color is light gray.
  • manufacturer's comment: Best operating results are achieved when reclosers are protected with surge arresters. On line applications, arrester protection is recommended on both sides of a recloser. If protection is to be provided on one side only, then it should be on the source side. In substations, arresters should be located on the load side. Cooper Power Systems, distribution-class surge arresters provide excellent protection for the Type VSO recloser.
Read More
Inquire
Compare for selected.
  • nominal voltage: 34.5 kV
  • Maximum Continuous Current: 560 A
  • Maximum Interrupting Current (symmetrical): 16000 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Oil Insulated
  • Remote lockout indicator:
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories:
  • weight:
    • Weight without control : 1130 lbs.
    • Weight with pole-top frame : 1193 lbs.
    • Weight with substation frame : 1271 lbs.
  • Finish/color: The recloser head is an aluminum casting. The tank is fabricated of heavy-gauge steel and is finished with a corrosion-inhibiting-epoxy prime coat, followed by a finish coat of thermosetting acrylic paint. Finish color is light gray.
  • manufacturer's comment: Best operating results are achieved when reclosers are protected with surge arresters. On line applications, arrester protection is recommended on both sides of a recloser. If protection is to be provided on one side only, then it should be on the source side. In substations, arresters should be located on the load side. Cooper Power Systems, distribution-class surge arresters provide excellent protection for the Type VSO recloser.
Read More
Inquire
Compare for selected.
  • nominal voltage: 34.5 kV
  • Maximum Continuous Current: 560 A
  • Maximum Interrupting Current (symmetrical): 12000 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?):
  • Remote lockout indicator:
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories:
    • Low-Voltage Closing and Transfer Switch
    • Bushings and Terminals
    • Continuous Current Accessory
    • Hardware : Oil-level sight gauge
  • weight: Weight-with oil : 990 lbs.
  • Finish/color: Heads are aluminum castings. Tanks are heavygauge steel, finished with polyester powder paint (Munsell 5BG 7.0/0.4; light gray is the standard color).
  • manufacturer's comment: Best operating results are achieved if reclosers are protected with surge arresters. On line applications, arrester protection is recommended on both sides of the recloser. (If protection is on one side only, it should be on the source side.) In substations, arresters should be on the load side. Cooper Power Systems distribution-class arresters provide excellent protection and are available with mounting brackets to fit Kyle reclosers
Read More
Inquire
Compare for selected.
  • nominal voltage:
  • Maximum Continuous Current: 800 A
  • Maximum Interrupting Current (symmetrical): 12500 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Solid dielectric insulated
  • Remote lockout indicator:
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories:
  • weight: Weight less bracket : 325 lbs. (148 kg).
  • Finish/color: Painted with a Munsell 7.0GY3.29/1.5 green finish.
  • manufacturer's comment:

    Applications

    • Sectionalizing schemes
    • Distributed automatic transfer
    • Distribution automation
    • Circuit breaker alternative
    • Relay protection
    • Revenue grade metering
    • Open bus ties
Read More
Compare or Request Quote for selected.
  • nominal voltage:
  • Maximum Continuous Current: 800 A
  • Maximum Interrupting Current (symmetrical): 12500 A
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Solid dielectric insulated
  • Remote lockout indicator:
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories:
  • weight: Weight (for a single phase module less bracket) : 125 lbs. (57 kg)
  • Finish/color: Painted with a Munsell 7.0GY3.29/1.5 green finish.
  • manufacturer's comment:

    Applications

    • Sectionalizing schemes
    • Distributed automatic transfer
    • Distribution automation
    • Circuit breaker alternative
    • Relay protection
    • Revenue grade metering
    • Open bus tie
Read More
Compare or Request Quote for selected.
  • nominal voltage: 38 kV
  • Maximum Continuous Current: 800 A
  • Maximum Interrupting Current (symmetrical): 12500 A RMS/ 16000 A RMS
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Sulphur Hexaflouride (SF6) Gas
  • Remote lockout indicator: Available (WSOS)
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories: Mounting arrangement (Pole mount, Substation frame), Control cable, Concrete pole clamps and Bushing boots.
  • weight: 249 kg (with pole mount bracket)
  • Finish/color:
  • manufacturer's comment: Recloser can be mounted closer to pole if lightning arresters are pole mounted. Optional substation mounting frame available on request.
Read More
Compare or Request Quote for selected.
  • nominal voltage: 38 kV
  • Maximum Continuous Current: 800 A
  • Maximum Interrupting Current (symmetrical): 12500 A RMS
  • load-interrupting current (asymmetrical):
  • Insulation material (i.e. oil, air epoxy?): Sulphur Hexaflouride (SF6) Gas
  • Remote lockout indicator: Available (WSOS)
  • Standard bushing leakage distance to ground:
  • Alternative bushing leakage distance to ground:
  • Available factory installed accessories: Mounting arrangement (Pole mount, Substation frame), Control cable, Concrete pole clamps and Bushing boots.
  • weight: 249 kg (with pole mount bracket)
  • Finish/color:
  • manufacturer's comment:

    The Nu-Lec Industries automatic circuit reclosers provide many outstanding advantages to the user. New and innovative features have been made possible by the intimate way the pole mounted circuit breaker and control cubicle work together.

    WSOS is the Nu-Lec Industries Switchgear Operating System software based on Microsoft Windows®. It provides easy access to all switchgear functions from opening/closing, through configuring protection and communication parameters to accessing measurement and analytical data. By using a desktop or portable PC engineers can manage a large number of reclosers either remotely via a communications link or locally via a serial port or Ethernet connection.

Read More
Compare or Request Quote for selected.
Select up to 5 products from above to compare or request more information.

Tags:

Please Login or Register to Create Tags